Electrical Conduits : SHK British Standard GI Conduits
Place Inquiry
SHK BS 4568 GI Conduits Class 4 & Class 3


SHK British Standard Electrical Galvanized Iron (G.I.) Conduit


Standard : BS 4568 Part 1 (1940)
  BS 50086 Part 1 (1998)
  BS 61386 Part 1 (2008)
Features

: Easy Wire Pushing and Pulling
  High grade epoxy coating makes it easy for for wire pulling and protects against corrosion

  Easy Coupling and fast installation
  Sharp, precise thread cuts makes the installation faster and moisture tight

  Fast and Accurate Bending
  High quality steel is used with high frequency welding to avoid any cracks while bending

  Standard quality
  Complete process is done in one continious process to maintain quality standards




SHK BS 4568 Class 4 G.I. Conduit - Hot Dipped Galvanized


Charecteristics : High Corrosion protection both from Inside and Outside surface of the conduit
  Hot Dipped Galvanized for harsh extream atmospheric condition
  Supplied with one Coupler with each leght for faster installation at site
  Threading as per BS standards using Metric size scaling system 
Applications : Suitable for exterior use
  Areas where high corrossion protection is required for cables/wires
  Recommended in areas with high level of humidity
  Other areas such as areas near chemical plants and Coastal areas & Car Parkings

Size (mm)
Outside Dia
Min           Max
Nominal Thickness
Length w/o Coupling
Cat No.
20 mm
19.7
20.0
1.6±0.15
±2.90 kg
SHK BS4-020
25 mm
24.6
25.0
1.6±0.15
±3.70 kg
SHK BS4-025
32 mm
31.6
32.0
1.6±0.15
±5.40 kg
SHK BS4-032
38 mm
37.5
38.0
1.6±0.15
±6.18 kg
SHK BS4-038
50 mm
49.5
50.0
1.6±0.15
±8.35 kg
SHK BS4-050
* Standard Length of each conduit is 3.75mtrs as per BS Standard



SHK BS 4568 Class 3 G.I. Conduit - Electro-Galvanized


Charecteristics : Heavy Corrosion protection from Outside surface of the conduit
  Electro-Galvanized protection for corrosion
  Supplied with one Coupler with each leght for faster installation at site
  Threading as per BS standards using Metric size scaling system 
Applications : Suitable for Semin Outdoor use
  Areas where corrossion protection is required for cables/wires
  In areas where mechanical protection is required for cables from any damage

Size (mm)
Outside Dia
Min           Max
Nominal Thickness
Length w/o Coupling
Cat No.
20 mm
19.7
20.0
1.6±0.15
±2.90 kg
SHK BS3-020
25 mm
24.6
25.0
1.6±0.15
±3.70 kg
SHK BS3-025
32 mm
31.6
32.0
1.6±0.15
±5.40 kg
SHK BS3-032
38 mm
37.5
38.0
1.6±0.15
±6.18 kg
SHK BS3-038
50 mm
49.5
50.0
1.6±0.15
±8.35 kg
SHK BS3-050
* Standard Length of each conduit is 3.75mtrs as per BS Standard



Cables Capacity of Conduit

The following tables give guidance on the calculation of the number of single core PVCinsulated cables which can be locateed in various sizes of conduit.

The table deal with two particular cases
1.Single-core PVCinsulated cables in straight runs exceeding 3 meters in length.
2.Single-core PVC insulated cables in straight runs exceeding 3 meters in length or in runs of any length with bends or sets


Staright runs not exceeding 3 meters in length

For each types of cables used obtains the cable factor from table 1. Sum all the cable factors and compare with the conduit factors given in table 2

The condiut sizes which will accomadate the cables are those with a conduit factors equal to or greater than the sum of the cable factors


Type of Conductor
Conductor cross-sectional area mm sq
Factor
Solid
1
1.5
2.5
22
27
39
Stranded
1.5
2.5
4
6
10
31
43
58
88
146
Table 1 Cable Factors for short straight runs

Conduit Dia in mm
Factor
16
20
25
32
290
460
800
1400
Table 2 Cable Factor for short straight runs

These tables are based on the 16th edition of the I.E.E. Wiring Regulations Appendix 12.

Sraight runs not exceeding 3 meters in length or runs of any length or runs of any length incorprating bends and sets
for each type of cable used obtains the cable factors from table 3. sum all the cable factors and compare with the conduit factorgiven in table 4 for the relevant lenght of run and the nuber of bends and sets in than run.

Type of Conductor
Conductor cross-sectional area mm sq
Factor
Solid
or
Stranded
1
1.5
2.5
4
6
10
16
22
30
43
58
105
Table 3 Cable Factors for long straight runs or runs incorporating bends

Spacing of supports for conduits

The following table gives guidance on the spacing of support for conduit

Nominal size of conduit mm
Max horizontal Distance mm
Max Vertical Distance mm
16
17mm – 25mm
26mm – 40mm
Over 40mm
0.75
1.75
2.00
2.25
1.00
2.00
2.25
2.50

This table is based on the 16th edition of the I.E.E. Wiring Regulations Appendix 11
These tables are for guidance ONLY and account needs to be taken of future Wiring needs

Note:
For Sale in the MENA Region
Middle East - UAE (Abu Dhabi, Dubai, Sharjah, Ajman, Fujairah, Ras Al Khaima, Umm Al Quwain), Bahrain (Manama), Qatar (Doha), Oman (Muscat), Kuwait, Yemen ++
Africa - Egypt, Morroco, Tunisia, Algeria ++



Disclaimer:
All information provieded are as per the regulations mentioned, site condition and situation might differ as per project requirement or current day factor. In either case follow Project Specifications and guidance.

Download Datasheet